This Wavin Monoline electrofusion reducing sleeve is used in water and gas systems to create a transition between two PE pipes or pressure fittings.

In addition to this electrofusion reducing sleeve, the electrofusion coupling range includes various accessories, such as:
  • Tools.
  • Links.
  • Welding machines.
  • Gaskets.
  • Transitions.

Properties

The Monoline reducing coupling has a maximum operating temperature of 20°C with a working pressure of 16 bar for water systems. For gas systems, the maximum operating temperature is 20°C with a working pressure of 10 bar.

Quality mark

The Wavin reducing coupling has Kiwa and Gastec QA certification. This makes the electrofusion fitting suitable for drinking water and gas.

Assembly

This reducing sleeve connects two pipes or fittings. To weld a PE pressure pipe to a weld coupling, you need a PE cleaner, a peeling device, clamps, and a welding machine. During welding, the coil in the electrofusion fitting heats up, fusing the two components together. This creates a strong, tensile-resistant, gas- and watertight connection.

The welding process
  • Place the reducing sleeve on the pipe and mark the spot with a marker.
  • Remove the reducing sleeve from the pipe, use the peeling device and remove the burrs.
  • Clean the area with PE cleaner and, if necessary, re-indicate the length.
  • Replace the reducing sleeve around the pipe and tighten the screws.
  • Connect the welding machine, scan the barcode and start the welding process.
  • Check the indicator pins, they should have come out all the way.
  • Disconnect and remove the welding cables and fixation clamps after the specified cooling time.
  • Wait at least 2 hours before pressurizing the piping system.

Want to buy electrofusion couplings or need more information?

The desired electrofusion transition sleeve can be ordered quickly and easily through our website or purchased at one of our locations. Still not sure which electrofusion transition sleeve is best for your situation? Contact one of our product specialists for free advice.